|
| |

State Fire Marshal Division  
444 Cedar Street, Suite 145,
St. Paul, Minnesota 55101-5145
Phone: 651/201-7200 FAX:
651/215-0525 TTY: 651/282/6555
Internet:
http://www.dps.state.mn.us
Smoke Detector Information

4/06
Minnesota
Statute 299F.32 Requirements:
-
Every dwelling and
dwelling unit must be provided with a smoke detector that meets the
requirements of the Minnesota State Fire Code. This includes single-family
homes, townhouses, apartment, hotels (containing six or more guest rooms),
lodging houses (containing five or less guest rooms), and similar occupancies.
-
Smoke detectors must be
mounted in accordance with the requirements of the Minnesota State Fire Code.
-
When activated, the smoke
detector must sound an alarm in the dwelling unit.
-
In new construction, smoke
detectors must be directly connected to the dwelling’s central power source.
-
The owner of the occupancy
is responsible for the maintenance of the smoke detector.
-
Occupants are required to
inform the owner of a nonfunctioning smoke detector within 24 hours of
discovering that the detector is not functioning.
-
It is a misdemeanor for an
occupant to willfully disable a smoke detector, or cause it to be
nonfunctioning, if such an action results in damage or injury to persons or
property.
-
Local governments may
establish ordinances for the installation of smoke detectors in single family
homes that are more restrictive than the requirements of statute. Local smoke
detector ordinances may be enforced through a truth-in-lending housing
inspection.
The Minnesota State Fire
Code Requirements:
-
In homes built prior to
March 31, 2003. Smoke detectors must be installed in hallways or areas
that provide access to each separate sleeping area.
-
In homes built on or
after March 31, 2003. A smoke detector must be installed in each sleeping
room in addition to a point centrally located in the corridor or area
providing access to each separate sleeping area. Where more than one smoke
alarm is required to be installed in a single family home, the smoke alarms
must be interconnected so that the activation of one alarm will activate all
the alarms in the home.
-
In homes constructed
prior to August 1, 1989. Smoke detectors may be battery powered only.
-
In homes constructed on
or after August 1, 1989 and before March 31, 2003. Smoke detectors must
hardwired to the home’s permanent primary wiring, without a disconnecting
switch. When new bedrooms are created, the detector in the new bedroom must
receive its primary power supply from a centralized power source and be
equipped with a battery backup.
-
In homes constructed on
or after March 31, 2003. Smoke detectors must receive their power from the
home’s permanent primary wiring when such wiring is served from a commercial
source and be equipped with a battery backup.
-
Smoke detector location
and spacing must be as follows, in addition to the manufacturer’s
instructions:
-
Smoke detectors in rooms
with ceiling slopes greater than 1-foot rise per 8 feet horizontally must
-
be located at the high
side of the room.
-
A smoke detector
installed in a stairwell must be located to ensure that smoke rising in the
stairwell cannot be prevented from reaching the detector by an intervening
door or other obstruction.
-
A smoke detector
installed in the basement must be located in close proximity to the stairway
-
leading to the floor
above.
-
Smoke detectors must be
mounted on the ceiling at least 4 inches from a wall or on a wall with the
top of the detector not less than 4 inches, or more than 12 inches, below
the ceiling.
-
Smoke detectors must not
be installed within kitchens, garages, or in other spaces where temperatures
can fall below 32°F, or exceed 100°F.
-
Smoke detectors must not
be located within 3 feet of supply registers of a forced air heating or
cooling system, and doors to a kitchen or bathroom with a tub or shower.
-
For peaked ceilings, the
smoke detector must be installed within 3 feet of the peak.
|